Pressure calculation for fan applications

Products

Related information

Plug fan applications - fan and box size requirements
Applications for plug fans - K-value and constant airflow applications
Fan Parallel Calculation
Fan Noise Calculation
Pressure calculation for fan applications
Difference between forward tilting impeller and backward tilting impeller

full pressure

Full pressure = static pressure + dynamic pressure

Static pressure outside the machine

Outside static pressure △P=Rm*L(1+k) Pa

Style:

Rm-Frictional resistance loss per unit length of duct, Pa/m;

L-The total length of the air supply pipe of the farthest air supply outlet plus the total length of the return pipe of the farthest air return outlet, m;

k- Ratio of local resistance loss to frictional resistance loss.

When the elbow tee is less, take k=1.0~2.0;

Elbow tee more, take k = 3.0 ~ 5.0

This formula is a simple estimation formula, if you need to optimize the calculation, it is recommended to use the hydrostatic compounding method

Calculations, see Practical Heating and Air Conditioning Design Manual (Second Edition) 11.6.3 P1157 for details.

Static pressure in the machine

Static pressure inside the machine = sum of resistance of each functional section (except fan section)

Functional section air resistance of combined air conditioner (Pa) (when the surface wind speed is 2.5m/s)

The following values are for reference only, specific values are recommended to consult the supplier

Primary filters 50

Intermediate filters 150

High efficiency filter 250

Coil (single row) 30

Chip/microplate anechoic section 60/30